Refusing a TCP Port 2222 connection is normal for an all-EtherNet/IP device that never supported classic CSPv4 to the PLC-5. I haven't worked on a PanelView 800 for a while so my comments might just be conjecture. If you just click on the icon or folder entry it does open/close because there were no arguments for it to process.

rslinx classic inhibit connection

To use TCPING, you have to open a CMD prompt window, then navigate to the folder where TCPING is located, then execute the command "TCPing 192.168.1.103 44818". Both with a crossover cable and a normal CAT 5e patch cable. I'd like to try a factory settings reset as the last option, but I'm starting to think it might just be the PanelView as plugging in the ethernet directly to my laptop bears similar results.

rslinx classic inhibit connection

I did verify that the IP address is unique, and it does fail to ping once unplugged. I thought it might have been an antivirus issue, but I disabled it and it still opens only for a moment. I'm also unable to get tcping to remain open. I think the firmware the PanelView is on doesn't support that (6.011) according to this () No I'm unable to connect or access the configuration through the browser. Narrow down your computer's NICs as well, of course shut off WiFi, disable any VPN connections. The EtherNet/IP driver uses a broadcast packet so you have to carefully select which IP network it is connected to, and firewalls and VPNs often prevent it from working. Try also making an exception in your firewall for TCP Port 2222, an older A-B protocol that the RSLinx Classic Ethernet Devices driver likes to try and fail before trying port 44818. I presume you've verified that the PanelView is at that 192.168.1.103 address by looking at its actual configuration screens, and eliminated the possibility of a duplicate IP by unplugging it and verifying that PING fails. In addition to good old built-in PING, try TCPing with the target port 44818, to see if your computer can get a TCP connection through its firewall (and the device at that IP is listening on that port, which all A-B devices should). Can you get a response from the PanelView 800 in a Web browser ?







Rslinx classic inhibit connection